A sample temperature control system using Peltier device is developed for volume resistivity measurement of dielectrics. Four Peltier devices are installed under a dielectric film to keep sample temperature from - 40 deg. to + 80 deg. As a result of heat conduction test under vacuum, we found that the temperature is controlled within 1 deg when the temperature setting is 80 deg, but in the case of negative temperature setting, the temperature does not decrease because heat dissipation is not adequate. We measured volume resistivity of polyimide film by a charge storage method with temperature variation. The results indicate that volume resistivity in dark current region decreases as the sample temperature increases as theoretically estimated.